A smooth signal can still be wrong
Add bias, noise and drift to a synthetic sensor. See what averaging changes, and what needs a reference.
Synthetic temperature signals
Turn down the scatter. Watch the offset stay.
Change one fault at a time, then widen the moving average. The light orange trace is the raw test signal, dark orange is its moving average, and teal is the reference.
Assumptions and limits
The reference changes from 20 to 22 °C over 60 seconds, sampled at 10 Hz. The baseline adds a constant +5 °C bias and noise strength 0.8 °C, with zero drift and a 21-sample trailing average. The reference is exact in this teaching model. Real references have uncertainty. A trailing average introduces lag, so the reported smoothed error compares two equally filtered traces.
Smoothing can reduce random scatter. It cannot identify the true temperature without other information or establish calibration.
What did the checks miss?
This fixed challenge set is separate from the controls above. The simple tests use roughness > 0.4 °C, absolute mean reference error > 1 °C, or absolute reference-error slope > 0.02 °C/s. These are teaching thresholds, not instrument acceptance criteria. The spike and flatline cases escape these checks.
| Fault added | Roughness alone | With reference checks | Missed |
|---|---|---|---|
| noise | flagged | roughness | none in this case |
| bias | missed | reference offset | none in this case |
| drift | missed | reference offset; reference drift | none in this case |
| spike | missed | not flagged | spike |
| flatline | missed | not flagged | flatline |
Download the computed table · Download the Python experiment · All synthetic data and assumptions
Which fault can survive smoothing?